1.
Purpose
1.1
The purpose of this document is to define good practice and to establish a
reasonable approach for the performance of an inspection of a
commercial property.
2.
Definitions
2.1
Core definitions
2.1.1
Commercial Property - A commercial property is defined as the building
structures and improvements located on a parcel of commercial real
estate. These may include structures such as buildings with
residential units operated for profit, mixed use buildings, strip malls, motels,
factories, storage facilities, restaurants, and office buildings.
2.1.2
Inspection - The inspection is defined as the process of an inspector
collecting information through visual observation during a walk-through
survey of the subject property, conducting research about the
property, then generating a meaningful report about the condition of the
property based on the observations made and research conducted by the
inspector. A commercial inspection requires the inspector to make
observations, conduct research, and report findings.
2.1.2.1
Observations - Observations are defined as those potential items of interest
noted by the inspector during the walk-through survey portion of the
inspection.
2.1.2.2
Research - Research is defined as the process of gathering information
through document review and interview to augment the observations made
during the walk-through portion of the inspection. This research may
include reviewing readily available documents such as previous inspection
reports, building permits, code violation notices and environmental studies.
This research may also include interviews with readily available personnel such
as building managers, tenants and owners.
2.1.2.3 Report
- An inspection report is defined as a written communication
describing the issues discovered from observations made and
research conducted by the inspector that are, in the inspector's
opinion, are likely to be of interest to his/her client. A report
may contain photographs of observations made during the walk-through survey
portion of the inspection and/or copies of documents reviewed during the
research portion of the inspection.
2.2
Terminology commonly found in commercial property inspection reports
·
Above
Grade Wall: A wall more that is mostly above grade and enclosing
conditioned space.
·
Access:
That which enables a device, appliance or equipment to be reached.
·
Access
Panel: A closure device used to cover an opening into a duct, an enclosure, or
equipment.
·
Accessible:
Can be approached or entered by the inspector safely, without difficulty, fear
or danger.
·
Accessibility:
Level of access a building offers people with disabilities.
·
Accessory
Structure: An additional building to the primary building.
·
Activate:
To turn on, supply power, or enable systems, equipment, or devices to become
active by normal operating controls. Examples include turning on the gas or
water supply valves to fixtures and appliances or activating
electrical breakers or fuses.
·
Actual
Knowledge: The knowledge possessed by an individual as opposed to that
discovered through document review.
·
Addition:
An extension or increase in the conditioned space of a building.
·
Adverse
Conditions: Conditions that may be dangerous for the inspector and
may limit the walk-through survey portion of the inspection.
·
Adversely
Affect: To constitute, or potentially constitute, a negative or destructive
impact.
·
Air
Intake: An opening in a building's envelope whose purpose is to allow outside
air to be drawn in to replace inside air.
·
Aisle: An
exit access component that provides a path of egress travel.
·
Alarm
Signal: A signal indicating an emergency, such as a fire, requiring
immediate action.
·
Alarm
System: Warning devices, installed or free-standing, including but not limited
to: carbon monoxide detectors, flue gas and other spillage detectors, security
equipment, ejector pumps and smoke alarms.
·
Alteration: Any
construction or renovation to an existing structure other than a repair or
addition. Also, a change in a mechanical system.
·
Appliance:
Utilization equipment, generally other than industrial, that is installed or
connected as a unit to perform one or more functions.
·
Approved:
Acceptable to the authority having jurisdiction. Also, accepted by
an internationally recognized organization such as InterNACHI.
·
Arc-Fault
Circuit Interrupter: A device intended to provide protection from the effects
of arc faults by recognizing characteristics unique to arcing and by
functioning to de-energize the circuit when an arc fault is detected.
·
Authority
Having Jurisdiction (AHJ): An organization, office, or individual responsible
for enforcing the requirements of a code or standard, or for approving
equipment, materials, an installation, or a procedure. The AHJ is
often the building owner, health department, insurance agent, or fire
Marshall.
·
Automatic:
That which provides a function without the necessity of human intervention.
·
Automatic
Fire-Extinguishing System: A system of devices and equipment which automatically
detects a fire and discharges in an attempt to put it out.
·
Automatic
Sprinkler System: An automated sprinkler system for fire protection
purposes.
·
Balcony:
Exterior floor projecting from and supported by a structure without additional
independent supports.
·
Band
Joist: Dimensional lumber used as a perimeter joist of the building framing.
·
Basement:
That portion of a building which is partly or completely below grade.
·
Basement
Wall: A wall of a building that is mostly below grade.
·
Bathroom:
A room containing plumbing fixtures such as a water closet, urinal, bathtub, or
shower.
·
Bedroom:
A room used for sleeping purposes.
·
Bonding:
The permanent joining of metallic parts to form an electrically conductive path
that ensures electrical continuity and the capacity to conduct safely any fault
current likely to be imposed.
·
Branch
Circuit: The circuit conductors between the final overcurrent device protecting
the circuit and the outlet(s).
·
Building:
The primary building subject of the commercial inspection.
·
Building
Code: Rules and regulations adopted by the governmental authority having
jurisdiction over the construction and/or remodeling of the commercial
property.
·
Building
Department: Local authority having jurisdiction over the construction,
alteration, and use of a property.
·
Building
Envelope: The enclosure that defines the heated/cooled area of a
building, namely the exterior walls and roof.
·
Building
Systems: Components, assemblies and systems which are a part of the
overall building and property such as pavement, flatwork, structural
components, roofing, exterior walls, plumbing, HVAC, electrical components,
fire prevention, etc.
·
Built-in:
Permanently installed.
·
Certified
Commercial Inspector (CCI): A professional designation
and a U.S. federal certification mark administered by the International
Association of Certified Home Inspectors, Inc. (InterNACHI).
·
Chimney:
A structure containing one or more flues for removing gases to the outside
atmosphere.
·
Cleanout: An
accessible opening in the drainage system used for the removal of possible
obstructions and for inspections. An opening in a chimney that
provides access to the flue for cleaning purposes.
·
Clearance:
The minimum distance through air measured between the surface of something
heat-producing and the surface of something combustible.
·
Clearly
Identifiable: Capable of being recognized by a person of normal vision.
·
Client:
The party that retains the inspector and pays for the inspection.
·
Code
Official: The officer or other government designated authority charged
with enforcement of building codes.
·
Combustible:
Describes any material that will burn.
·
Commercial
Cooking Appliances: Appliances used in a commercial food service
establishment for heating or cooking food.
·
Commercial
Property: The building structures and improvements located on a
parcel of commercial real estate. These may include structures such
as buildings with residential units operated for profit, mixed use buildings,
strip malls, motels, factories, storage facilities, restaurants, and office
buildings.
·
Component:
A permanently installed or attached fixture, element or part of a system.
·
Concealed: Rendered
inaccessible by the structure or finish of the building. Wires in
concealed raceways are considered concealed, even though they may become
accessible by withdrawing them.
·
Condition:
The plainly visible and conspicuous state of being of a material object or
thing.
·
Conditioned
Space: An area or room within a building being heated or cooled.
·
Connector:
The pipe that connects a fuel-burning appliance to a chimney.
·
Consultant: A
person with particular expertise in a subject who assists the inspector
with portions of the inspection.
·
Contamination:
An impairment of the quality of the potable water.
·
Crawlspace:
The area within the confines of the foundation and between the ground and the
underside of the lowest floor structural component.
·
Cross
Connection: Any connection between two otherwise separate piping systems, one
of which contains potable water and the other which contains something which
could contaminate the potable water.
·
Crown:
The sloped top of a masonry chimney designed to shed water away from the flue;
also called a splay or a wash.
·
Damper:
A valve or plate for controlling draft or flow of gases, including air, in a
vent or ductwork. A typically manually-operated plate for
controlling draft in a flue.
·
Decorative:
Ornamental; not required for the operation of essential systems and components
of a building.
·
Deck: Exterior
floor system supported on at least two opposing sides by an adjoining structure
and/or post, piers, or other independent supports.
·
Defensible
Space: An area around a building designed to slow the rate of an advancing
wildfire.
·
Deferred
Maintenance Items: Deficient items that cannot be remedied with routine
maintenance, generally caused by neglect.
·
Describe:
To report in writing a system or component by its type, or other observed
characteristics, to distinguish it from other components used for the same
purpose.
·
Destructive:
An act of demolishing, damaging, or probing any system, structure, or
component, or to dismantle any system or component that would not be taken
apart by an ordinary person in the course of normal maintenance.
·
Determine:
To arrive at an opinion or conclusion pursuant to examination.
·
Disconnected:
Shut down.
·
Dismantle:
To open, take apart or remove any component, device or piece that would not
typically be opened, taken apart or removed by an ordinary occupant.
·
Duct:
A passageway, tube, or conduit utilized for the transmission of air and vapors.
·
Due
Diligence: A level of care in the inspection process which varies
depending upon the scope of work agreed upon by the inspector and his/her
client.
·
Dwelling
Unit: A single unit providing complete, independent living facilities,
including permanent provisions for living, sleeping, eating, cooking and
sanitation.
·
Easily
Visible: Describes systems, items, and components that are both conspicuous and
in plain sight, absent of the need for intrusive inspection techniques,
probing, disassembly or the use of special equipment.
·
Easement:
That portion of a land or property reserved for use by a person or agency other
than the owner of the property.
·
Egress: A
means of exiting.
·
Emergency
Shutoff Valve: A valve designed to shut off the flow of gases or liquids.
·
Energy
Analysis: A method for estimating the annual energy use of a building.
·
Energy
Recovery Ventilation System: A system that uses air-to-air heat exchangers
to recover energy from exhaust air for the purpose of preheating or precooling
outdoor air prior to supplying the air to a space.
·
Engineering
Service: Any professional service or creative work requiring engineering
education, training, and experience and the application of special knowledge of
the mathematical, physical and engineering sciences to such professional
service or creative work as consultation, investigation, evaluation, planning,
design and/or supervision of construction for the purpose of assuring compliance
with the specifications and design, in conjunction with structures, buildings,
machines, equipment, works or processes.
·
Enter:
To access or go into an area to observe visible components.
·
Evaluate:
To assess the systems, structures or components of a building.
·
Evidence:
Plainly visible and conspicuous material objects or other things presented to
the senses that would tend to produce conviction in the mind of an ordinary
person as to the existence or non-existence of a fact.
·
Examine:
To visually examine. To look for and identify material physical deficiencies in
systems, structures, or components of a building through a non-intrusive
physical inspection. See Inspect.
·
Existing: Buildings,
facilities or conditions which are already in existence. This standard is
designed to be used to inspect existing commercial properties.
·
Exit
Discharge: The portion of a means of egress between the termination of an exit
and a public way.
·
Exposed: Capable
of being inadvertently touched by a person because it is not suitably guarded,
isolated, or insulated.
·
Exterior
Property: The open space on the property.
·
Exterior
Wall: An outside wall of a building, either above or below grade.
·
Extermination:
The control or elimination of insects, rats, vermin, or other pests.
·
Fenestration:
Fenestration includes products with glass and non-glass glazing materials
including skylights, roof windows, vertical windows, opaque doors, glazed
doors, or glazed block.
·
Fire
Apparatus Access Road: A road, fire lane, public street, private street,
or parking lot lane that provides access from a fire station to a
facility.
·
Fire
Code Official: The fire chief or other authority charged with the enforcement
of a code.
·
Fire
Department Master Key: A special key carried by fire department officials which
will open key boxes on commercial properties.
·
Fire
Resistance Rating: The time that materials or assemblies can withstand fire
exposure.
·
Fire
Wall: A wall separating buildings or subdividing a building to prevent the
spread of fire.
·
Fireplace
Lintel: A horizontal, noncombustible member that spans the top of the
fireplace opening.
·
Fixture:
Component.
·
Flood
Level Rim: The edge of a fixture from which water overflows.
·
Floor
Area, Gross: The floor area within the inside perimeter of the exterior
walls.
·
Floor
Area, Net: The actual occupied area not including accessory areas such as
corridors, stairways, restrooms, mechanical rooms and closets.
·
Flue: A
passage through which gasses move from the fire chamber to the outer air.
·
Foundation:
The base upon which the structure or wall rests; usually masonry, concrete, or
stone, and generally partially underground.
·
Function:
The action for which an item, component, or system is specially fitted or used
or for which an item, component or system exists; to be in action or perform a
task.
·
Functional:
Performing, or able to perform, a function.
·
Functional
Drainage: The emptying of a plumbing fixture in a reasonable amount of time
without overflow when another fixture is drained simultaneously.
·
Functional
Flow: A reasonable flow of water supply at the highest and farthest fixture
from the building main when another fixture is operated simultaneously.
·
Further
Evaluation: A degree of examination beyond that of a typical and customary
non-intrusive physical examination.
·
Fusible
Link: A form of fixed temperature heat detecting device sometimes used to
restrain the operation of an electrical or mechanical control until a certain
temperature is reached usually signifying a fire.
·
Garbage:
The animal or vegetable waste resulting from preparation or consumption of
food.
·
Grease:
Animal fat, vegetable shortening, or oil used in preparing food or resulting
from cooking.
·
Grounded:
Connected to earth or to some conducting body that serves in place of the earth.
·
Grounded,
Effectively: Intentionally connected to earth through a ground connection or
connections of sufficiently low impedance and having sufficient current
carrying capacity to prevent the buildup of voltages that might otherwise
result in undue hazards to connected equipment or to persons.
·
Ground-Fault
Circuit Interrupter (GFCI): A device intended for the protection of personnel
that functions to de-energize a circuit.
·
Grounding
Electrode: A device that establishes an electrical connection to the earth.
·
Habitable
Space: Space in a structure for living, sleeping, eating or cooking.
Bathrooms, closets, halls, storage areas and utility spaces are not considered
habitable spaces.
·
Hearth:
The floor within a fireplace.
·
Hearth
Extension: Noncombustible material in front of and at the sides of a fireplace
opening.
·
Heated
Slab: Slab-on-grade construction in which the heating elements are placed
within or under the slab.
·
Hood:
A device that directs and captures grease-laden vapors and gases from a cooking
appliance.
·
Immediate
Cost: Estimated cost of remedying an existing safety hazard or repairing a
system or component that will likely fail within a year.
·
Humidistat:
A device used to automatically control relative humidity.
·
Imminent
Danger: A condition which could cause serious or life-threatening injury or
death.
·
Infestation:
The presence of insects, rats, vermin, or other pests.
·
Infill:
Area of the railing system bounded by the railing posts, cap, rail,
and the deck.
·
Infiltration:
The uncontrolled inward air leakage into a building.
·
Inspected
Property: The readily accessible areas of the buildings, site, items,
components, and systems included in the inspection.
·
Inspection:
The process of an inspector collecting information through visual
observation during a walk-through survey of the subject
property, conducting research about the property, and then generating
a meaningful report about the condition of the property based on the
observations made and research conducted by the inspector. A
commercial inspection requires the inspector to make observations, conduct
research, and report findings.
·
Inspector:
One who performs the commercial property inspection.
·
Installed:
Attached or connected such that the installed item requires tool for removal.
·
Interview:
To discuss with those who have knowledge about the subject property.
·
Intrusive:
Destructive.
·
Key
Box: A lockable device which permits the fire department to access the building
in an emergency.
·
Labeled:
Devices, equipment, or materials to which have been affixed a label, seal,
symbol or other identifying mark of product evaluation.
·
Ledger:
Dimensional lumber attached to the building framing and used for
supporting the section of a deck adjacent to the building.
·
Life
Expectancy: Average function time in years assuming regular maintenance.
·
Listed:
Equipment, materials, or services included in a list published by an
organization that is acceptable to the authority having jurisdiction and
concerned with evaluation of products or services, that maintains periodic
inspection of production of listed equipment or materials or periodic
evaluation of services, and whose listing states the either the equipment,
material, or service meets appropriate designated standards or has been tested
and found suitable for a specified purpose.
·
Mantel:
A shelf or horizontal ornament above a fireplace opening.
·
Manual:
Capable of being operated by a person.
·
Material:
Having significant importance as in material defect. This term is
reserved for describing things of significant importance.
·
Material
Defect: A condition of a commercial property or any portion of it that would
have a significant adverse impact on the value of the real property or that
involves unreasonable risk to people on the property. The fact that a
structural element, system or subsystem is near, at or beyond the end of the
normal useful life of such a structural element, system of subsystem is not
by itself a material defect.
·
Means
Of Egress: A continuous and unobstructed path out of a building to a public
way.
·
Mold: A
form of fungus. Some molds can cause disease in humans.
·
Noncombustible:
A substance that will not burn when subjected to fire.
·
Normal
Operating Controls: Devices such as thermostats that would be operated by
ordinary occupants which require no specialized skill or knowledge.
·
Observations:
Those potential items of interest noted by the inspector during the
walk-through survey portion of the inspection.
·
Observe:
To see through visually directed attention.
·
Obvious:
A condition or fact not likely to be ignored or overlooked.
·
Occupancy
Load: The number of people permitted in a building based on the means of
egress.
·
Occupant:
Any individual living, sleeping, or having possession of a space within a building.
·
Operate:
To cause systems to function or turn on with normal operating controls.
·
Operational:
Systems or components capable of being safely operated.
·
Oral
Consultation: A limited visual inspection of specific systems, structures,
or components of a building where no written report is prepared by the
inspector and the inspector's findings, opinions, conclusions, and
recommendations are orally communicated by the inspector to the client.
·
Owner:
Any person, agent, operator, firm or corporation having a legal or equitable
interest in a property.
·
Panelboard:
A panel including buses and automatic overcurrent devices designed to
be placed in a cabinet accessible only from the front.
·
Permanently
Installed: Fixed in place (e.t. screwed, bolted, or nailed), as distinct from
components, systems, or appliances considered portable or freestanding.
·
Phase
I: A type of fireplace and chimney inspection that exceeds the standards
required by a traditional home inspection.
·
Physical
Deficiency: A major defect, a significant deferred maintenance
item, a component or system that has exhausted most or all of
its remaining useful life (regardless of its actual life
expectancy), a safety concern, or anything that could potentially
cause the need for an expensive repair.
·
Pitch:
Angle or inclination, usually of a roof.
·
Plenum:
An air compartment or chamber which connects one or more ducts and forms part
of an air distribution system.
·
Premises:
A lot, plot, parcel of land, property, or building.
·
Pressure
Drop: The loss in pressure due to friction or obstruction in pipes, valves,
fittings, regulators and burners and the length of pipes and the number of
elbows.
·
Pressure
Regulator: A device placed in a gas line for reducing, controlling and
maintaining the pressure downstream of the device.
·
Primary
Building: A building that an inspector has agreed to inspect, excluding all
accessory buildings with the exception of the primary parking structure.
·
Primary
parking Structure and Surfaces: A building and appurtenant surfaces for the purpose
of vehicle storage associated with the primary building.
·
Public
Way: A street, alley or yard open to the outside and leading to a public area.
·
Publicly
Available Information: Information that is accessible or available to
anyone upon request.
·
Raceway:
An enclosed channel or conduit designed expressly for holding wires
or cables.
·
Ramp:
A sloped walking surface.
·
Readily
Accessible: Describes the area of the subject property that has been made
available to the inspector at the time of the walk-through survey portion of
the inspection, and/or an item or component if, in the judgment of the
inspector, it is capable of being safely observed without the need of portable
ladders, the removal of obstacles, the detachment or disengagement of
connecting or securing devices, or other unsafe or difficult procedures to gain
access and/or a document that has been made available to the inspector for use
in the research portion of the inspection.
·
Readily
Ascertainable: Describes information that is available to the inspector within
reasonable time at a nominal cost so that it can be practically
reviewable during the research portion of the inspection.
·
Readily
Available: Describes the information, personnel, and documents that
are made available quickly to the inspector.
·
Receptacle:
A contact device installed at the outlet for the connection of an attachment
plug.
·
Recreational
Facilities: Spas, saunas, steam baths, swimming pools, tennis courts, playground
equipment, and other exercise, entertainment or athletic facilities.
·
Remaining
Useful Life: A subjective estimate or guess made by the inspector based
upon his observations and experience as to the number of remaining years
that a component will be functional before needing replacement.
·
Removable:
Capable of being transferred to another location easily.
·
Replacement
Air: Air deliberately brought into a structure to compensate for the air being
consumed or expelled.
·
Repair:
The reconstruction or renewal of any part of an existing building.
·
Report: The written
communication describing the issues discovered from observations
made and research conducted by the inspector and which, in the
inspector's opinion, are likely to be of interest to his/her client.
A report may contain photographs or digital images of observations made
during the walk-through survey portion of the inspection and/or copies of
documents reviewed during the research portion of the inspection.
·
Representative
Number: A sufficient number to serve as a typical or characteristic example of
the item(s) inspected.
·
Representative
Sampling: A small quantity of components of any system or structure, enough
like others in its class or kind, to serve as an example of its class or kind.
·
Research: The
process of gathering information through the review of documents and interviews
to augment the observations made during the walk-through portion of the
inspection. This research may include reviewing readily available documents
such as previous inspection reports, building permits, code violation notices
and environmental studies. This research may also include interviews with
readily available personnel such as building managers, tenants and owners.
·
Roof
Assembly: A system designed to provide weather protection and
including the roof covering, underlayment, roof deck, insulation, vapor
retarder and interior finish.
·
Rubbish:
Waste materials other than garbage.
·
Scope
of Work: Work that deviates from this standard depending on budget, time constraints,
purpose of the inspection, age of the subject property, and risk tolerance of
the client which the inspector and client have agreed to.
·
Screw
Lamp Holder: A lamp base that requires a screw-in-type lamp such as a
compact florescent, incandescent, or tungsten-halogen bulb.
·
Short
Term Cost: Estimated cost of repairs which may not require immediate
attention, but which should not be delayed for more than 2 years.
·
Shut
Down: Turned off, unplugged, inactive, not in service, or not operational.
·
Single-wall,
metal chimney: A typically field-constructed chimney not permitted in
1- and 2-family dwellings.
·
Sleeping
Unit: A room or space in which people sleep.
·
Smoke
Alarm: A single or multiple alarm responsive to smoke and not connected to a
sprinkler system.
·
Smoke
Detector: A device that senses particles of combustion.
·
Solid-fuel:
Wood, coal, pellets, and other materials that can be burned for
heat.
·
Special
Consultant: A person with particular expertise in a subject who assists
the inspector with portions of the inspection.
·
Special
Equipment: Any tools or devices other than those normally used by an inspector
to perform a typical and customary, non-invasive, physical examination of the
systems, structures, and components of a building, including, but not limited
to: levels, probes, meters, video or audio devices and measuring devices.
·
Standard: Often
used to mean InterNACHI' Standards of Practice for Inspecting Commercial
Properties.
·
Storefront:
A nonresidential system of doors and windows typically at floor level of a
commercial building.
·
Structural
Component: A component which supports the building's dead and live loads.
·
Structure:
An assemblage of various systems and components to function as a whole.
·
Subject
Property: The commercial property that is the subject of the inspection.
·
Suggested
Remedy: An opinion offered as to a course of action to repair a
deficiency. Suggested remedies are outside the scope of a commercial
inspection.
·
Sump:
A tank or pit that receives sewage or waste water typically located below the
drain system and so must be emptied by mechanical means.
·
Sump
Pump: An automatic water pump powered by a motor and typically controlled by a
float for the removal of waste water from a sump pit.
·
System:
An assembly of various components which function as a whole.
·
Technically
Exhaustive: A comprehensive and detailed examination beyond the scope of a
commercial property inspection which might involve, but would not be
limited to: specialized knowledge or training, special equipment, measurements,
calculations, testing, research, analysis, meters, scaffolding, dismantling,
probing, or troubleshooting. Also, where the cost of obtaining
information or the time required to conduct a portion of the inspection and
prepare that portion of the inspection report could outweigh the likely
usefulness of the information obtained or could be detrimental to the orderly
and timely completion of the client's transaction.
·
Thermostat:
An automatic control device used to maintain temperature at a set point.
·
Thimble. The
tube or lining through a wall that a connector passes through to
enter a flue or that a flue passes through to exit a roof.
·
Timely
Access: Access to the subject property and documentation required by
the inspector to perform the inspection.
·
Toilet
Room: A room containing a water closet or urinal but not a bathtub or shower.
·
Trap:
A fitting that provides a liquid seal to prevent the emission of sewer gases
and odors.
·
Tree
Crown: The branches growing out from a tree including twigs and foliage.
·
Unsafe: A
condition of an area, system, component, or procedure which, in the inspector’s
opinion, poses a significant risk to the personal safety of either the
occupants and/or him/herself. The danger to the occupants may be due to damage,
deterioration, improper installation, a change in accepted standards, etc. The
danger to the inspector may be due to electrical, fuel, height,
sewage, water, debris, weather or other environmental conditions, and may
restrict his/her access and limit or prevent the inspection.
·
Valve:
A device used in piping to control the gas or liquid supply downstream of the
device.
·
Vapor
Retarder: A vapor resistant material, membrane, or covering such as foil,
plastic sheeting, or insulation facing which limits the amount of moisture
vapor that passes through a material or wall assembly.
·
Ventilation:
The natural or mechanical process of supplying and removing air from any space.
·
Verify:
To confirm or substantiate.
·
Visible:
That which may be easily observed during the walk-through survey portion of the
inspection.
·
Walk-Through
Survey: That portion of the inspection where the inspector makes
non-intrusive, visual observations of readily accessible areas of the
subject property.
·
Wall
Protector: Noncombustible shield between a wall and anything
heat-producing for the purpose of reducing required
clearance.
·
Workmanlike:
Executed in a skilled manner.
·
Yard:
An open space on the same lot with a building.
·
Zone:
The space or group of spaces within a building with
conditioning controlled by a single device.
2.3
Common abbreviations and acronyms used in commercial property inspection
reports
·
ADA:
Americans with Disabilities Act.
·
AHJ:
Authority having jurisdiction.
·
BUR:
Built-up roofing.
·
CCI:
Certified Commercial Inspector.
·
CMI:
Certified Master Inspector.
·
CPI:
Certified Professional Inspector.
·
CO:
Certificate of occupancy.
·
COMSOP:
Commercial Standards of Practice.
·
CSA:
Canadian Standards Association.
·
EIFS:
Exterior insulation and finish system.
·
EPA:
Environmental Protection Agency.
·
HVAC:
Heating, ventilation and air conditioning.
·
IAC2:
International Association of Certified Indoor Air Consultants.
·
IAQ:
Indoor air quality.
·
InterNACHI:
International Association of Certified Home Inspectors.
·
ICC:
International Code Council.
·
IR:
Infrared.
·
MICB:
Master Inspector Certification Board.
·
NFPA:
National Fire Protection Association.
·
PE:
Professional Engineer.
·
RUL:
Remaining useful life.
2.4
Other inspection related terms
Other inspection related terms can be found by visiting InterNACHI's searchable
online Glossary at www.nachi.org/glossary.htm
3.
Use
3.1
Royalty-free use
Although
this standard is protected by copyright and other laws, the International
Association of Certified Home Inspectors, Inc. (InterNACHI) hereby
grants non-exclusive, royalty-free license to all members
of InterNACHI and their clients and all public authorities,
government agencies and government employees throughout the world to
use this code as desired including making copies, posting,
transmitting, and incorporating into reporting software, free of charge,
without the need for pre-approval, provided that each use
is clearly attributed to InterNACHI.
Acceptable
examples of attribution include "performed in accordance with InterNACHI's
Commercial SOP," "based on InterNACHIcomsop-2008" or "see www.internachi.org/comsop."
Nothing
in this license shall preclude InterNACHI from modifying this standard and
users should regularly check for the latest revision at www.nachi.org/comsop.htm which
supersedes earlier versions.
3.2
Conflicts with other standards, codes, local laws, and manufacturer's
instructions.
There
likely exist other standards, codes, local laws, and manufacturer's
instructions that differ or are in conflict with this standard and with
each other. Although this standard does not require an inspector to know
or discover all the provisions that may pertain to every situation, this
standard does require an inspector, if aware of such conflicts, to author
the inspection report based on the requirements that provide the greatest
protection of life and property, in the inspector's judgment. This
standard is not intended to usurp or abridge adopted codes or ordinances.
3.3
Substantial compliance
The
inspector shall substantially abide by this standard unless otherwise
agreed to in writing by the inspector and client.
3.4
Disclaimer of liability
InterNACHI
administers the process in the development of its standards. InterNACHI
does not independently test, evaluate, or verify the accuracy of any
information or the soundness of any judgments contained in its standards.
InterNACHI disclaims liability for any personal injury, property or other
damages of any nature whatsoever, whether special, indirect, consequential or
compensatory, directly or indirectly resulting from the publication, use of, or
reliance on this document. InterNACHI also makes no guaranty or warranty
as to the accuracy or completeness of any information published herein.
Anyone
using this document should rely on his or her own independent judgment or, as
appropriate, seek the advice of a competent professional in determining the
exercise of reasonable care in any given circumstances.
4.
Inspection
4.1
Objective
The objective
of an inspection is to provide written communication describing
the issues discovered from observations made and
research conducted by the inspector and that, in the inspector's opinion, are
likely to be of interest to his/her client and to enhance the client's
information and knowledge about the commercial property to improve
decision making for buying, selling, maintaining, or improving the
property.
4.2 Who
may perform the inspection
Any
portion of the inspection including the walk-through survey, research, and
report generation may be performed by the inspector, his/her staff, or any
consultant hired by the inspector. This standard recognizes that for the
majority of commercial inspections, the inspector is likely an individual with
a general, well rounded knowledge of commercial properties and that the
inspector or client may want to augment the inspector's skills with specialty
consultants who have particular expertise in certain areas. The decision
to hire specialty consultants will of course rely on budget and time
constraints as well as the risk tolerance of the client.
4.3
Varying levels of due diligence
This
standard is designed as a baseline from which the inspector and
client can develop and agree to a scope of work that may deviate from this
standard depending on budget, time constraints, purpose of the inspection, age
of the subject property, and risk tolerance of the
client. The level of due diligence should be set where the
cost, in time and money, of acquiring information about the subject
property will not likely exceed the value of that
information. Therefore an inspection performed in accordance with
this standard will not be technically exhaustive.
4.3.1
Sample language for use when defining the scope of work
"The
inspection will be performed in accordance with InterNACHIcomsop-2008
except that... "
4.3.2
Representative observations
In
recognizing that the client likely has the goal of acquiring information about
the subject property at a cost, in time and money, that does not exceed the
value of that information, representative observations are not just
permitted by this standard, but recommended as well.
4.4
Uncertainty
The
client should understand that no inspection report is completely
accurate. A report is only the written communication of the
observations made and research conducted by the inspector.
The report contains those items which in the inspector's
opinion are likely to be of interest to his/her client.
4.5
Subjectivity
The
client should understand that the inspection report is, to a large
degree, the subjective opinions of the inspector based
on his/her observations and research within the limits of access,
time, and budget and without the aid of special equipment or meters and
without dismantling, probing, testing, or troubleshooting and
without detailed knowledge of the commercial property, its
components or its systems. The inspection report is not much more
than a subjective professional opinion.
4.6
Not an architectural or engineering service
An
inspector performing a commercial inspection in accordance with this
standard is not practicing architecture or engineering.
4.7
Not a warranty, guarantee or insurance policy
The
inspection is not a warranty and the inspection report is merely the
written communication of the inspector's subjective opinion on the condition of
the subject property.
5.
Research
5.1
Objective
The
objective of research, including the review of documents and the
performing of interviews, is to augment the information obtained during
the walk-through survey and to provide supporting documentation to the
inspection report.
5.2
Document procurement
It
is the client's responsibility to obtain copies of all documents and provide
them for the inspector. These documents are most often obtained from the
seller or from local government offices. The inspector is not responsible
for gathering or paying for copies of appropriate documents to be reviewed
unless these tasks are specifically assigned to the inspector in the scope of
work agreement.
5.3
Documents to be reviewed and included in the inspection report
The
inspector should review all documents provided by the client and owner.
The inspector should also make an inquiry and review of any other documents
that can be reasonably procured on-site or from the building owner or
manager such as certificates of occupancy, building code violation notices,
repair invoices, and warranties. The inspector is not required to uncover
and review information that is not provided or cannot be
reasonably ascertained or acquired on-site. Copies of documents that
the inspector believes may be of interest to the client and copies of documents
that support the inspector's opinions should be included in the inspection
report.
5.3.1
Examples of documents the inspector may want to request for review
·
Accessibility
surveys
·
Appraisals
·
Building
plans
·
Certificates
of occupancy
·
Citations
·
Deck
age records, plans and construction permits.
·
Deck
and balcony maintenance, power washing, painting, treating, repair and
modification history
·
Emergency
evacuation plans
·
Environmental
studies
·
Evacuation
drill records
·
Fire
detection test and maintenance records
·
Fire
door inspection reports
·
Fire
prevention plans
·
Fire
extinguisher service records
·
Fire
records
·
Flame
resistant certificates
·
Flood
plane maps
·
Floor
plans
·
Kitchen grease
cleaning records
·
Kitchen
post fire inspections
·
Maintenance
records
·
Manufacturer's
installation instructions
·
Notices
·
Permits
·
Power
washing records
·
Previous
inspection reports
·
Proposals
·
Rent
records
·
Repair
estimates/invoices
·
Safety
inspection records
·
Seller
disclosures
·
Sprinkler
head replacement records
·
Utility
bills
·
Warranties
5.4
Interviews
The
inspector should identify and interview the person(s) with the most knowledge
about the condition of the building. Typically this will be the building
owner or manager. Unless otherwise agreed to in the scope of work
agreement, it is the responsibility of the client to arrange to have this
person(s) on hand for interview by the inspector on the day of the
walk-through survey.
5.5
Pre-inspection questionnaires
The
inspector may request that the owner, building manager and/or client fill
out pre-inspection questionnaires to gather information. The inspector
may rely that these responses are truthful. In cases where
parties refuse to fill out questionnaires in writing, the inspector may
interview the parties and fill out the questionnaires for them. The
inspector should note in the report if he/she filled out the questionnaire
based on an interview and whether such interview was performed in person, by
telephone, or by email. Copies of all responses to such questionnaires
should be included in the inspection report.
5.6
Reliance
The
level of accuracy of information varies depending on its source. The
inspector may rely on information obtained to the extent that the information
appears to be accurate and complete. This standard does not require the
inspector to independently verify the accuracy of the documents
reviewed by the inspector or included in the report nor the statements
made by those interviewed by the inspector.
5.7
Fraud
The
inspector is not a fraud investigator and this standard does not require the
inspector to look for intentionally hidden deficiencies in the subject
property. The inspection report is supplementary to the seller's
disclosures.
5.8
Previously generated reports
A
previously generated inspection report should be treated no differently than
any other document reviewed during the research portion of the inspection and
like information collected from any other source, information obtained
from a previously generated report should reference its source in the new
inspection report. No portion of a previously generated report should be
used as a substitute for the new inspection report.
6.
Walk-Through Survey
6.1
Objective
The
objective of the walk-through survey is to allow the inspector to visually observe
the subject property, gather information and note items of interest.
6.2
Access responsibility
It
is the client's responsibility to arrange for the inspector to
receive timely access to the subject property for the walk-through
survey portion of the inspection and access to all documents and
interviewees needed for the research portion of the inspection. This
includes access to all documents, information, and previously generated
reports in the client's possession. The inspector is not responsible for obtaining,
reviewing, or providing information should the source withhold,
impede or delay access. Anything that hinders the
inspector's access should be noted in the report.
6.3
Revisits
It
is expected that the inspector will perform only one walk-through survey
per inspection report. However, it may be necessary for the inspector to
revisit certain areas of the subject building after performing the research
portion of the inspection.
6.4
Inspector safety
It
is the responsibility of the inspector to perform the walk-through
survey safely.
6.5
Observations
6.5.1
Roof
I.
The inspector should inspect from ground level, or eaves or roof top (if a roof
top access door exists):
A. The roof covering.
B. For presence of exposed membrane.
C. Slopes.
D. For evidence of significant ponding.
E. The gutters.
F. The downspouts.
G. The vents, flashings, skylights, chimney and other roof penetrations.
H. The general structure of the roof from the readily accessible panels, doors
or stairs.
I. For the need for repairs.
II.
The inspector is not required to:
A. Walk on any pitched roof surface.
B. Predict service life expectancy.
C. Inspect underground downspout diverter drainage pipes.
D. Remove snow, ice, debris or other conditions that prohibit the observation
of the roof surfaces.
E. Move insulation.
F. Inspect antennae, lightning arresters, de-icing equipment or similar
attachments.
G. Walk on any roof areas that appear, in the opinion of
the inspector, to be unsafe.
H. Walk on any roof areas if it might, in the opinion of
the inspector, cause damage.
I. Perform a water test.
J. Warrant or certify the roof.
K. Walk on any roofs that lack rooftop access doors.
6.5.2
Exterior
I.
The inspector should inspect:
A. The siding, flashing and trim.
B. All exterior doors, decks, stoops, steps, stairs, porches, railings, eaves,
soffits and fascias.
C. And report as in need of repair any safety issues
regarding intermediate balusters, spindles, or rails for steps, stairways,
balconies, and railings.
D. A representative number of windows.
E. The vegetation, surface drainage and retaining walls when these are likely
to adversely affect the structure.
F. The exterior for accessibility barriers.
G. The storm water drainage system.
H. The general topography.
I. The parking areas.
J. The sidewalks.
K. Exterior lighting.
L. The landscaping.
M. And determine that a 3-foot clear space
exists around the circumference of fire hydrants.
N. And describe the exterior wall covering.
II.
The inspector is not required to:
A. Inspect or operate screens, storm windows, shutters,
awnings, fences, outbuildings, or exterior accent lighting.
B. Inspect items, including window and door flashings, which are not visible or
readily accessible from the ground.
C. Inspect geological, geotechnical, hydrological and/or soil conditions.
D. Inspect recreational facilities.
E. Inspect seawalls, break-walls and docks.
F. Inspect erosion control and earth stabilization measures.
G. Inspect for proof of safety type glass.
H. Determine the integrity of the thermal window seals or
damaged glass.
I. Inspect underground utilities.
J. Inspect underground items.
K. Inspect wells or springs.
L. Inspect solar systems.
M. Inspect swimming pools or spas.
N. Inspect septic systems or cesspools.
O. Inspect playground equipment.
P. Inspect sprinkler systems.
Q. Inspect drain fields or drywells.
R. Inspect manhole covers.
S. Operate or evaluate remote control devices or test door
or gate operators.
6.5.3 Wood
decks and balconies
I.
The inspector should inspect:
A. With
naked eye, for deck and balcony members that are noticeably out
of level or out of plumb.
B. For
visible decay.
C. For
paint failure and buckling.
D.
For nail pullout (nail pop).
E.
For fastener rust, iron stain, and corrosion.
F. And
verify that flashing was installed on the deck side of the ledger board.
G.
For vertical members (posts) that have exposed end grains.
H.
For obvious trip hazards.
I.
For non-graspable handrails.
J. Railings
for height less than the 36 inch minimum.*
K. Guardrails
and infill for openings that exceed the 4 inch maximum.*
L. Open
tread stairs for openings that exceed the 4 and 3/8 inch maximum.*
M.
Triangular area between guardrails and stairways for openings that exceed
the 6 inch maximum.*
N. Built-up and
multi-ply beam spans for butt joints.
O. For
notches in the middle third of solid-sawn wood spans.
P. For
large splits longer than the depths of their solid-sawn wood members.
Q. For
building egresses blocked, covered, or hindered by deck construction.
R. For
the possibility of wetting from gutters, downspouts, or sprinklers.
*See www.nachi.org/stairways.htm for formal standards
(compliance verification in entirety not required).
II.
The inspector is not required to:
A.
Discover insect infestation or damage.
B.
Inspect, determine, or test the tightness or adequacy of fasteners.
C.
Determine lumber grade.
D.
Measure moisture content.
E.
Inspect for or determine bending strength.
F.
Inspect for or determine shear stress.
G.
Determine lag screw or bolt shear values.
H.
Calculate loads.
I.
Determine proper spans or inspect for deflections.
J.
Discover decay hidden by paint.
K.
Verify that flashing has been coated to prevent corrosion.
L.
Determine that post to footing attachments exists.
M.
Dig below grade or remove soil around posts.
N.
Crawl under any deck with less than 3 feet headroom or remove deck skirting to
acquire access.
O.
Determine proper footing depth or frost line.
P.
Verify proper footing size.
Q.
Perform pick tests.
R.
Perform or provide any architectural or engineering service.
S.
Use a level or plum bob.
T.
Use a moisture meter.
U.
Predict service life expectancy.
V.
Verify compliance with permits, codes or formal standards.
W.
Inspect for disabled persons accessibility barriers.
X.
Determine if deck blocks, covers, or hinders septic tank or plumbing access.
Y.
Determine easement encroachment compliance.
6.5.4
Basement, foundation and crawlspace
I.
The inspector should inspect:
A. The basement.
B. The foundation.
C. The crawlspace.
D. The visible structural components.
E. And report on the location of under-floor access openings.
F. And report any present conditions or clear indications of active water
penetration observed by the inspector.
G. For wood in contact or near soil.
H. And report any general indications of foundation
movement that are observed by the inspector, such as but not limited to
sheetrock cracks, brick cracks, out-of-square door frames or floor slopes.
I. And report on any cutting, notching and boring of
framing members which may present a structural or safety concern.
II.
The inspector is not required to:
A. Enter any crawlspaces that are not readily accessible or
where entry could cause damage or pose a hazard to the inspector.
B. Move stored items or debris.
C. Operate sump pumps.
D. Identify size, spacing, span, location or determine adequacy of foundation
bolting, bracing, joists, joist spans or support systems.
E. Perform or provide any engineering or architectural service.
F. Report on the adequacy of any structural system or component.
6.5.5 Heating
and ventilation
I.
The inspector should inspect:
A. Multiple gas meter installations, such as a building
with multiple tenant spaces, and verify that each meter is clearly and
permanently identified with the respective space supplied.
B. The heating systems using normal operating controls
and describe the energy source and heating method.
C. And report as in need of repair heating systems which do not
operate.
D. And report if the heating systems are deemed inaccessible.
E. And verify that a permanent means of access with
permanent ladders and/or catwalks is present for equipment and appliances on
roofs higher than 16 feet.
F. And verify the presence of level service
platforms for appliances on roofs with a 25 percent slope or greater.
G. And verify that a luminaire and receptacle
outlet are provided at or near the appliance.
H. And verify that the system piping appears to be sloped
to permit the system to be drained.
I. For connectors, tubing and piping that might be
installed in a way that exposes them to physical damage.
J. Wood framing for cutting, notching and boring that might
cause a structural or safety issue.
K. Pipe penetrations in concrete and masonry building
elements to verify that they are sleeved.
L. Exposed gas piping for identification by a yellow label
marked "Gas" in black letters occurring at intervals of 5 feet or
less.
M. And determine if any appliances or equipment with
ignition sources are located in public, private, repair or parking garages or
fuel-dispensing facilities.
N. And verify that fuel-fired appliances are not located in
or obtain combustion air from sleeping rooms, bathrooms, storage closets or
surgical rooms.
O. For the presence of exhaust systems in occupied areas
where there is a likelihood of excess heat, odors, fumes, spray, gas, noxious
gases or smoke.
P. And verify that outdoor air intake openings are located
at least 10 feet from any hazardous or noxious contaminant sources such as
vents, chimneys, plumbing vents, streets, alleys, parking lots or loading
docks.
Q. Outdoor exhaust outlets for the likelihood
that they may cause a public nuisance or fire hazard due to smoke, grease,
gases, vapors or odors.
R. For the potential of flooding and evidence of past
flooding that could cause mold in ductwork or plenums.
S. Condensate drains.
II.
The inspector is not required to:
A. Inspect or evaluate interiors of flues or chimneys, fire
chambers, heat exchangers, humidifiers, dehumidifiers, electronic air
filters, solar heating systems, fuel tanks, safety devices, pressure
gauges, or control mechanisms.
B. Determine the uniformity, temperature, flow, balance, distribution, size,
capacity, BTU, or supply adequacy of the heating system.
C. Light or ignite pilot flames.
D. Activate heating, heat pump systems, or other heating systems when ambient
temperatures or when other circumstances are not conducive to safe operation or
may damage the equipment.
E. Override electronic thermostats.
F. Evaluate fuel quality.
G. Verify thermostat calibration, heat anticipation or
automatic setbacks, timers, programs or clocks.
H. Inspect tenant owned or maintained heating
equipment.
I. Determine ventilation rates.
J. Perform capture and containment tests.
K. Test for mold.
6.5.6 Cooling
I.
The inspector should inspect:
A. Multiple air conditioning compressor installations,
such as a building with multiple tenant spaces, and verify that
each compressor is clearly and permanently identified with the
respective space supplied.
B. The central cooling equipment using normal operating
controls.
C. And verify that a luminaire and receptacle outlet
are provided at or near the appliance.
D. And verify that a permanent means of access with
permanent ladders and/or catwalks is present for equipment and appliances on
roofs higher than 16 feet.
E. And verify the presence of level service
platforms for appliances on roofs with a 25 percent slope or greater.
F. Wood framing for cutting, notching and boring that might
cause a structural or safety issue.
G. Pipe penetrations in concrete and masonry building
elements to verify that they are sleeved.
H. Piping support.
I. For connectors, tubing and piping that might be
installed in a way that exposes them to physical damage.
J. For the potential of flooding and evidence of past
flooding that could cause mold in ductwork or plenums.
K. Condensate drains.
II.
The inspector is not required to:
A. Inspect or test compressors, condensers, vessels,
evaporators, safety devices, pressure gauges, or control mechanisms.
B. Determine the uniformity, temperature, flow, balance,
distribution, size, capacity, BTU, or supply adequacy of the cooling system.
B. Inspect window units, through-wall units, or electronic air filters.
C. Operate equipment or systems if exterior temperature is below 60 degrees
Fahrenheit or when other circumstances are not conducive to safe operation or
may damage the equipment.
D. Inspect or determine thermostat calibration, heat anticipation or automatic
setbacks or clocks.
E. Examine electrical current, coolant fluids or gases, or coolant leakage.
F. Inspect tenant owned or maintained cooling
equipment.
G. Test for mold.
6.5.7 Plumbing
I.
The inspector should inspect:
A. And verify the presence of and identify the location of
the main water shutoff valve to each building.
B. And verify the presence of a backflow prevention device
if, in the inspector's opinion, a cross connection could occur between water
distribution system and nonpotable water or private source.
C. The water heating equipment, including combustion air, venting, connections,
energy source supply systems, seismic bracing, and verify the presence or
absence of temperature-pressure relief valves and/or Watts 210 valves.
D. And flush a representative number of toilets.
E. And run water in a representative number of sinks, tubs, and showers.
F. And verify that hinged shower doors open outward from
the shower and have safety glass conformance stickers or indicators.
G. The interior water supply including a representative number of fixtures and
faucets.
H. The drain, waste and vent systems, including a representative
number of fixtures.
I. And describe any visible fuel storage systems.
J. The drainage sump pumps and test pumps with accessible floats.
K. And describe the water supply, drain, waste and main fuel shut-off valves,
as well as the location of the water main and main fuel shut-off valves.
L. And determine if the water supply is public or private.
M. The water supply by viewing the functional flow in several fixtures operated
simultaneously and report any deficiencies as in need of repair.
N. And report as in need of repair deficiencies in installation and
identification of hot and cold faucets.
O. And report as in need of repair mechanical drain-stops that are missing
or do not operate if installed in sinks, lavatories and tubs.
P. And report as in need of repair commodes that have cracks in the
ceramic material, are improperly mounted on the floor, leak, or have tank
components which do not operate.
Q .Piping support.
II.
The inspector is not required to:
A. Determine the adequacy of the size of pipes, supplies,
vents, traps, or stacks.
B. Ignite pilot flames.
C. Determine the size, temperature, age, life expectancy or adequacy of the
water heater.
D. Inspect interiors of flues or chimneys, cleanouts, water softening or
filtering systems, dishwashers, interceptors, separators, sump pumps, well
pumps or tanks, safety or shut-of valves, whirlpools, swimming pools, floor
drains, lawn sprinkler systems or fire sprinkler systems.
E. Determine the exact flow rate, volume, pressure, temperature, or adequacy of
the water supply.
F. Verify or test anti-scald devices.
G. Determine the water quality or potability or the reliability of the water
supply or source.
H. Open sealed plumbing access panels.
I. Inspect clothes washing machines or their connections.
J. Operate any main, branch or fixture valve.
K. Test shower pans, tub and shower surrounds or enclosures
for leakage.
L. Evaluate the compliance with local or state conservation or energy standards,
or the proper design or sizing of any water, waste or venting components,
fixtures or piping.
M. Determine the effectiveness of anti-siphon, back-flow prevention or
drain-stop devices.
N. Determine whether there are sufficient clean-outs for effective cleaning of
drains.
O. Evaluate gas, liquid propane or oil storage tanks.
P. Inspect any private sewage waste disposal system or component within such a
system.
Q. Inspect water treatment systems or water filters.
R. Inspect water storage tanks, pressure pumps, ejector pumps, or bladder
tanks.
S. Evaluate wait time for hot water at fixtures,
or perform testing of any kind on water heater elements.
T. Evaluate or determine the adequacy of combustion air.
U. Test, operate, open or close safety controls, manual
stop valves and/or temperature or pressure relief valves.
V. Examine ancillary systems or components, such as, but
not limited to those relating to solar water heating or hot water circulation.
W. Determine the presence or condition of polybutylene
plumbing.
6.5.8 Electrical
I.
The inspector should inspect:
A. The service drop/lateral.
B. The meter socket enclosures.
C. The service entrance conductors and report on any
noted conductor insulation or cable sheath deterioration.
D. The means for disconnecting the service main.
E. The service entrance equipment and report on any
noted physical damage, overheating, or corrosion.
F. And determine the rating of the service amperage.
G. Panelboards and overcurrent devices and report on any noted physical
damage, overheating, corrosion, or lack of accessibility or
working space (minimum 30 inches wide, 36 inches deep, 78 inches high in front
of panel) that would hamper safe operation, maintenance or
inspection.
H. And report on any unused circuit breaker panel
openings that are not filled.
I. And report on absent or poor labeling.
J. The service grounding and bonding.
K. A representative number of switches, receptacles,
lighting fixtures and AFCI protected receptacles. Although a visual
inspection, the removal of faceplates or other covers or luminaires (fixtures)
to identify suspected hazards is permitted.
L. And report on any noted missing or
damaged faceplates or box covers.
M. And report on any noted open junction boxes or
open wiring splices.
N. And report on any noted switches and receptacles that
are painted.
O. And test all Ground Fault Circuit Interrupter (GFCI)
receptacles and GFCI circuit breakers observed and deemed to be GFCI's during
the inspection using a GFCI tester where possible.
P. And report the presence of solid conductor aluminum
branch circuit wiring if readily visible.
Q. And report on any tested GFCI receptacles in
which power was not present, polarity is incorrect, the cover is not
in place, the ground fault circuit interrupter devices are not installed
properly or do not operate properly, any evidence of arcing or
excessive heat, or where the receptacle is not grounded or is not secured to
the wall.
R. And report the absence of smoke detectors.
S. And report on the presence of flexible cords being
improperly used as substitutes for the fixed wiring of a structure or
running through walls, ceilings, floors, doorways, windows, or under carpets.
II.
The inspector is not required to:
A. Insert any tool, probe or device into the main
panelboard, sub-panels, subpanels, distribution panelboards, or electrical
fixtures.
B. Operate electrical systems that are shut down.
C. Remove panelboard cabinet covers or dead front covers if they are not
readily accessible.
D. Operate overcurrent protection devices.
E. Operate non-accessible smoke detectors.
F. Measure or determine the amperage or voltage of the main service equipment
if not visibly labeled.
G. Inspect the fire or alarm system and components.
H. Inspect the ancillary wiring or remote control devices.
I. Activate any electrical systems or branch circuits which are not energized.
J. Operate or reset overload devices.
K. Inspect low voltage systems, electrical de-icing tapes, swimming pool wiring
or any time-controlled devices.
L. Verify the service ground.
M. Inspect private or emergency electrical supply sources, including but not
limited to generators, windmills, photovoltaic solar collectors, or battery or
electrical storage facility.
N. Inspect spark or lightning arrestors.
O. Inspect or test de-icing equipment.
P. Conduct voltage drop calculations.
Q. Determine the accuracy of labeling.
R. Inspect tenant owned equipment.
S. Inspect the condition of or determine the ampacity
of extension cords.
6.5.9 Fireplaces
I.
The inspector should inspect:
A.
Fireplaces, and open and close the damper doors if readily accessible and
operable.
B. Hearth extensions and other permanently installed components.
C. And report as in need of repair deficiencies in the lintel, hearth and
material surrounding the fireplace, including clearance from combustible
materials
II.
The inspector is not required to:
A. Inspect the flue or vent system.
B. Inspect the interior of chimneys or flues, fire doors or screens, seals
or gaskets, or mantels. C. Determine the need for a chimney sweep.
D. Operate gas fireplace inserts.
E. Light pilot flames.
F. Inspect automatic fuel feed devices.
G. Inspect combustion and/or make-up air devices.
H. Inspect heat distribution assists whether gravity controlled or fan
assisted.
I. Ignite or extinguish fires.
J. Determine draft characteristics.
K. Move fireplace inserts, stoves, or firebox contents.
L. Determine adequacy of draft, perform a smoke test or dismantle or remove any
fireplace component.
M. Perform an NFPA inspection.
N. Determine the appropriateness of any installation.
6.5.10 Attic
ventilation and insulation
I.
The inspector should inspect:
A.
The insulation in unfinished spaces.
B. The ventilation of attic spaces.
C. Mechanical ventilation systems.
D. And report on the general absence or lack of insulation.
II.
The inspector is not required to:
A. Enter the attic or any unfinished spaces that are not
readily accessible or where entry could cause damage or pose a safety hazard to
the inspector in his or her opinion.
B. Move, touch, or disturb insulation.
C. Move, touch or disturb vapor retarders.
D. Break or otherwise damage the surface finish or weather seal on or around
access panels and covers.
E. Identify the composition or exact R-value of insulation material.
F. Activate thermostatically operated fans.
G. Determine the types of materials used in insulation or wrapping of pipes,
ducts, jackets, boilers, and wiring.
H. Determine the adequacy of ventilation.
6.5.11 Doors,
windows and interior
I.
The inspector should:
A. Open and close a representative number of doors and
windows.
B. Inspect the walls, ceilings, steps, stairways, and railings.
C. Inspect garage doors and garage door openers.
D. Inspect interior steps, stairs, and railings.
E. Inspect all loading docks.
F. Ride all elevators and escalators.
G. And report as in need of repair any windows that are
obviously fogged or display other evidence of broken seals.
II.
The inspector is not required to:
A. Inspect paint, wallpaper, window treatments or finish
treatments.
B. Inspect central vacuum systems.
C. Inspect safety glazing.
D. Inspect security systems or components.
E. Evaluate the fastening of countertops, cabinets, sink tops and fixtures, or
firewall compromises.
F. Move furniture, stored items, or any coverings like carpets or rugs in order
to inspect the concealed floor structure.
G. Move drop ceiling tiles.
H. Inspect or move any appliances..
I. Inspect or operate equipment housed in the garage except as otherwise noted.
J. Verify or certify safe operation of any auto reverse or related safety
function of a garage door.
K. Operate or evaluate any security bar release and opening mechanisms, whether
interior or exterior, including their compliance with local, state, or
federal standards.
L. Operate any system, appliance or component that requires the use of special
keys, codes, combinations, or devices.
M. Operate or evaluate self-cleaning oven cycles, tilt guards/latches,
gauges, or signal lights.
N. Inspect microwave ovens or test leakage from microwave ovens.
O. Operate or examine any sauna, steam-jenny, kiln, toaster, ice-maker,
coffee-maker, can-opener, bread-warmer, blender, instant hot water dispenser,
or other ancillary devices.
P. Inspect elevators.
Q. Inspect remote controls.
R. Inspect appliances.
S. Inspect items not permanently installed.
T. Examine or operate any above-ground, movable, freestanding, or otherwise
non-permanently installed pool/spa, recreational equipment or
self-contained equipment.
U. Come into contact with any pool or spa water in order to determine the
system structure or components.
V. Determine the adequacy of spa jet water force or bubble effect.
W. Determine the structural integrity or leakage of a pool or spa.
X. Determine combustibility or flammability.
Y. Inspect tenant owned equipment or personal property.
6.5.12
Life-safety
I.
The inspector should:
A. Inspect
fire access roads and report on any obstructions or overhead wires lower than
13 feet 6 inches.
B.
Inspect the address or street number to determine that it is visible from
the street with numbers in contrast to their background.
C.
Inspect and determine that a 3-foot clear space exists around the circumference
of fire hydrants.
D.
Verify that hinged shower doors open outward from the shower and have safety
glass conformance stickers or indicators.
E.
Inspect to determine that the storage of flammable and combustible materials
are orderly, separated from heaters by distance or shielding so that ignition
cannot occur, and not stored in exits, boiler rooms, mechanical rooms, or
electrical equipment rooms.
F.
Inspect to determine that a "No Smoking" sign is posted in areas
where flammable or combustible material is stored, dispensed, or used.
G. Inspect
for the presence of fire alarm systems.
H. Inspect
for alarm panel accessibility.
I. Inspect
for the presence of portable extinguishers and determine that they are
located in conspicuous and readily available locations immediately available
for use and not obstructed or obscured from view.
J.
Inspect to determine that a portable fire extinguisher exists within a 30 foot
travel distance of commercial-type cooking equipment that uses cooking oil or
animal fat.
K.
Inspect to determine that manual actuation devices for commercial cooking
appliances exist near the means of egress from the cooking area,
42-48 inches above the floor, 10-20 feet away, and clearly identifying the
hazards protected.
L.
Inspect to determine that the maximum travel distance to a fire extinguisher is
75 feet.
M. Inspect
for the presence of sprinkler systems and determine if they were ever
painted other than at the factory.
N. Inspect
for the presence of emergency lighting systems.
O. Inspect
for exit signs at all exits and inspect for independent power sources such as
batteries.
P. Inspect
for the presence of directional signs where exit location is not obvious.
Q. Inspect
for the presence of signs over lockable exit doors stating "This Door
Must Remain Unlocked During Business Hours."
R. Inspect
for penetrations in any walls or ceilings that separate the exit corridors
and/or stairwells from the rest of the building.
S. Inspect
for fire separation doors that appear to have been blocked or wedged open
or that do not automatically close and latch.
T. Inspect exit
stairwell handrails.
U.
Inspect for exit trip hazards.
V.
Inspect for the presence of at least two exits to outside or one exit that
has a maximum travel distance of 75 feet.
W.
Inspect exit doorways to determine that they are not less than 32 inches in
clear width.
X.
Inspect to determine that the exit doors were not locked from the inside,
chained, bolted, barred, latched or otherwise rendered unusable at the time of
the inspection.
Y. Inspect
to determine that the exit doors swing open in the direction of egress travel.
Z. Inspect
the storage at the time of the inspections to determine if it is
potentially obstructing access to fire hydrants, fire extinguishers, alarm
panels, or electric panel boards, or if it is obstructing aisles,
corridors, stairways or exit doors, or if it is within 18 inches of sprinkler
heads or if it is within 3 feet of heat generating appliances or electrical
panel boards at the time of the inspection.
II.
The inspector is not required to:
A. Test alarm
systems or determine if alarms systems have been tested.
B. Inspect
or test heat detectors, fire suppression systems, or sprinkler systems.
C. Determine
combustibility or flammability of materials or storage.
D. Determine
the adequate number of fire extinguishers needed or their ratings.
E. Test
or inspect fire extinguishers, their pressure, or for the presence of
extinguisher inspection tags and/or tamper seals.
F. Inspect
or test fire pumps or Fire Department connections.
G. Inspect
or test cooking equipment suppression systems.
H. Determine
the operational time of emergency lighting or exist signs.
I.
Inspect for proper occupant load signs.
J.
Determine fire ratings of walls, ceilings, doors, etc.
K.
Inspect, test, or determine the adequacy of fire escapes or ladders.
L.
Inspect Fire Department lock boxes or keys.
M.
Determine flame resistance of curtains or draperies.
N. Inspect parking
and/or outdoor lighting.
O. Inspect
for unauthorized entry and/or crime issues.
P. Inspect
or test security systems.
Q. Inspect
for pet or livestock safety issues.
R. Inspect
for unsafe candle use or decoration hazards
S. Inspect
or test emergency generators
T. Test
kitchen equipment, appliances, or hoods.
U.
Verfiy that elevator keys exist or that they work properly.
6.5.13
Cooking area
I.
The inspector should:
A.
Verify that all smoke or grease-laden vapor producing cooking equipment such as
deep-fat fryers, ranges, griddles, broilers, and woks, is equipped with an
exhaust system.
B.
Inspect exhaust systems interior surface cleaning and inspection
accessibility.
C. Inspect
for grease buildup.
D. Verify
that hoods are made of steel or stainless steel.
E. Verify
that visible grease filters are arranged so that all exhaust air passes through
the filters.
F.
Verify that visible sections of exhaust ducts are not interconnected with
any other ventilation system.
G.
Verify that visual sections of exhaust ducts are installed without dips or
traps that might collect residues.
H. Verify
that exhaust ducts do not appear to pass through fire walls.
I.
Try to verify that exhaust ducts lead directly to the exterior of the building.
J.
Try to verify that exterior exhaust outlets do not discharge into walkways
or create a nuisance in the opinion of the inspector.
K.
Inspect to determine that a portable fire extinguisher exists within a 30 foot
travel distance of commercial-type cooking equipment that uses cooking oil or
animal fat.
L.
Inspect to determine that manual actuation devices for commercial cooking
appliances exist near the means of egress from the cooking area,
42-48 inches above the floor, 10-20 feet away, and clearly identifying the
hazards protected.
II.
The inspector is not required to:
A.
Determine proper clearances.
B.
Determine proper hood size or position.
C.
Test hoods.
D.
Test exhaust fans, test dampers, or measure airflow.
E.
Test fire extinguishers, fire-extinguishing equipment or fusible links.
F. Test
kitchen equipment, appliances, hoods or their gauges.
G.
Inspect or test grease removal devices, drip trays or grease filters.
H.
Inspect or test air pollution control devices or fume incinerators.
I.
Inspect or test kitchen refrigeration.
J.
Inspect for fuel storage issues.
K.
Inspect, test, or determine anything regarding food safety.
L.
Issue an opinion regarding cooking operating procedures.
7.
Report
7.1
Format
The
report must be in writing. This standard does not require any one
particular format. It is InterNACHI's opinion that the commercial
inspection industry and consumer clients are best served when inspectors
are free to compete through report generation innovation.
7.2
Date
The
report should be dated on the first page of the report.
7.3 Inspection
firm information
The
report should include the name and contact information of the inspection firm
on the first or second page.
7.4
Property address
The
report should include the address of the property inspected or a description of
the real estate sufficient for identification on the first or second page.
7.5
Total number of pages
The
report should indicate the total number of pages and attachments on the
first page of the report.
7.6
Brevity
Reports
should be concise, to the point, and avoid the inclusion of large amounts of
pre-printed material.
7.7
Legibility
Reports
should be typed or handwritten clearly.
7.8
Opinions of shutdown systems
The
inspector should still try to render an opinion of the condition of systems
even if they were shutdown or were not operational at the time of the
walk-through survey.
7.9
Obsolescence
The
client should only rely on the inspection report at the point in
time that the inspector's observations were being made and research was
being conducted. The client should deem the report as obsolete
to some extent, even while it is being prepared.
7.10
Site-specific
The
client should understand that an inspection performed in accordance with this
standard only relates to the observations made and research conducted.
Consequently this standard does not address issues such as business
operations at the subject property, deed encumbrances, neighborhood conditions,
etc.
7.11
Multiple buildings
An
inspection report produced in accordance with this standard may encompass
more than one building within a single report.
7.12
Cost to remedy
The
inspector is not required to provide repair estimates or opinions of costs to remedy.
The inspector may offer opinions about such costs as a courtesy but the
offering of these opinions is outside the scope of a commercial inspection.
8. Limitations, Exceptions and Exclusions
8.1.
Limitations:
I. An inspection is not technically exhaustive.
II. An inspection will not identify concealed or latent defects.
III. An inspection will not deal with aesthetic concerns or what could be
deemed matters of taste, cosmetic defects, etc.
IV. An inspection will not determine the suitability of the property for any
use.
V. An inspection does not determine the market value of the property or its
marketability.
VI. An inspection does not determine the insurability of
the property.
VII. An inspection does not determine the advisability or inadvisability of the
purchase of the inspected property.
VIII. An inspection does not determine the life expectancy
of the property or any components or systems therein.
IX. An inspection does not include items not permanently
installed.
X. These Standards of Practice apply only to commercial properties.
8.2.
Exclusions:
I.
The inspectors are not required to determine:
A. Property boundary lines or encroachments.
B. The condition of any component or system that is not readily accessible.
C. The service life expectancy of any component or system.
D. The size, capacity, BTU, performance, or efficiency of any component or
system.
E. The cause or reason of any condition.
F. The cause of the need for repair or replacement of any system or
component.
G. Future conditions.
H. The compliance with codes or regulations.
I. The presence of evidence of rodents, animals or insects.
J. The presence of mold, mildew or fungus.
K. The presence of air-borne hazards.
L. The presence of birds.
M. The presence of other flora or fauna.
N. The air quality.
O. The presence of asbestos.
P. The presence of environmental hazards.
Q. The presence of electro-magnetic fields.
R. The presence of hazardous materials including, but not limited to, the
presence of lead in paint.
S. Any hazardous waste conditions.
T. Any manufacturer's recalls or conformance with manufacturer's installation
or any information included for consumer protection purposes.
U. Operating costs of systems.
V. Replacement or repair cost estimates.
W. The acoustical properties of any systems.
X. Estimates of the cost of operating any given system.
Z. Resistance to wind, hurricanes, tornados, earthquakes or
seismic activities.
AA. Geological conditions or soil stability.
BB. Americans with Disabilities Act compliance.
II.
The inspectors are not required to operate:
A. Any system that is shut down.
B. Any system that does not function properly.
C. Or evaluate low voltage electrical systems such as, but not limited to:
1.
Phone
lines.
2.
Cable
lines.
3.
Antennae.
4.
Lights.
5.
Remote
controls.
D. Any system that does not turn on with the use of normal
operating controls.
E. Any shut off valves or manual stop valves.
F. Any electrical disconnect or over current protection devices.
G. Any alarm systems.
H. Moisture meters, gas detectors or similar equipment.
I. Sprinkler or fire suppression systems.
III.
The inspectors are not required to:
A.
Move any personal items or other obstructions, such as, but not limited to:
1.
Throw rugs.
2. Furniture.
3. Floor or wall coverings.
4. Ceiling tiles
5. Window coverings.
6. Equipment.
7. Plants.
8. Ice.
9. Debris.
10. Snow.
11. Water.
12. Dirt.
13. Foliage.
14. Pets
B. Dismantle, open, or uncover any system or component.
C. Enter or access any area which may, in the opinion of the inspector, be
unsafe.
D. Enter crawlspaces or other areas that are unsafe or not readily accessible.
E. Inspect or determine the presence of underground items such as, but not
limited to, underground storage tanks, whether abandoned or actively used.
F. Do anything which, in the inspector's opinion, is likely to be unsafe or
dangerous to the inspector or others or damage property, such as, but not
limited to, walking on roof surfaces, climbing ladders, entering attic spaces or interacting
with pets or livestock.
G. Inspect decorative items.
H. Inspect common elements or areas in multi-unit housing.
I. Inspect intercoms, speaker systems, radio-controlled, security devices or
lawn irrigation systems. J. Offer guarantees or warranties.
K. Offer or perform any engineering services.
L. Offer or perform any trade or professional service other
than commercial property inspection.
M. Research the history of the property, report on its potential for
alteration, modification, extendibility, or its suitability for a specific or
proposed use for occupancy.
N. Determine the age of construction or installation of any system structure,
or component of a building, or differentiate between original
construction and subsequent additions, improvements, renovations or
replacements thereto.
O. Determine the insurability of a property.
P. Perform or offer Phase 1 environmental audits.
Q. Inspect or report on any system or component
which is not included in these standards.
9.
Ethics
Inspectors
performing inspections in accordance to this standard must maintain a high
level of business ethics.
9.1
Duty to client
9.1.1
The inspector shall substantially follow this standard
unless the scope of work indicates otherwise.
9.1.2
The inspector shall not engage in any practices that could be damaging to
the client or bring discredit to the inspection industry.
9.1.3
The inspector shall be fair, honest, impartial, and act in good faith in
dealing with the client.
9.1.4
The inspector shall not discriminate on the basis of race,
color, religion, sex, national origin, familial status, or handicap and
shall comply with all federal, state and local laws concerning discrimination.
9.1.5
The inspector member shall be truthful regarding his/her services and
qualifications.
9.1.6
The inspector shall have no undisclosed conflict of interest with the client,
nor shall the inspector accept or offer any undisclosed commissions,
rebates, profits or other benefit, nor shall the inspector accept or offer
any disclosed or undisclosed commissions, rebates, profits or other benefit
from real estate agents, brokers or any third parties
having financial interest in the sale of the property nor shall the
inspector offer or provide any disclosed or undisclosed financial compensation
directly or indirectly to any real estate agent, real estate broker
or real estate company for referrals or for inclusion on lists of preferred
and/or affiliated inspectors or inspection companies.
9.1.7
The inspector shall not communicate any information about an inspection to
anyone except the client without the prior written consent of the client,
except in cases when the information may affect the safety of others or
violates a law or statute.
9.1.8
The inspector shall always act in the interest of the client, unless doing so
violates a law or statute.
9.1.9
The inspector shall use a written scope of work agreement that specifies
the services to be performed, the limitations of services and fees.
9.1.10
The inspector shall comply with all government rules and licensing
requirements in the jurisdiction where he/she conducts business.
9.1.11
The inspector shall not perform or offer to perform, for an additional
fee, any repairs or associated services to the structure for which
the inspector or inspector's company has prepared a commercial
inspection report, for a period of 12 months. This provision shall not include
services to components and/or systems which are not included in this standard.